Blind-Mate Quick Disconnects
Envicool Externally Retained Blind-Mate Coupling
A separately MQDB blind-mate construction with no integral lock, documented alignment guidance and model-specific flow and socket-end examples from an official catalogue.
- Retention
- No integral lock; externally fastened | Conditions: rack or module structure must provide retention
- Claimed alignment compensation
- plus or minus 1 mm | Conditions: manufacturer series claim; installed datum stack and specific size must be checked
- Size specific recommended flow
- MQDB02 2.1; MQDB03 4.6; MQDB04 8.5; MQDB04 MINI 8.5 L/min | Conditions: separate model rows, water at 20 degC, plug-to-socket, 5 m/s velocity criterion; not one family flow range
- Socket end examples
- MQDB02 UNF7/16-20; MQDB03 G1/4; MQDB04 G3/8 | Conditions: example model rows; plug ends differ; exact order code and mating drawing required
Envicool
Blind-Mate Quick Disconnects
Specifications
MQDB series
| Parameter | Documented value / configuration |
|---|---|
| Size specific socket plug end examples | For MQDB03, the socket table lists G1/4 socket MQDB03-1432-G14 and the plug table lists a 9 mm end MQDB03-7434-P9; the two half ends are different and code-specificConditions: Example order rows only; verify mating, equipment-side guidance and external retention |
| Listed shell and seal options | MQDB technical summary lists SUS316L shell and EPDM or FVMQ sealing-ring optionsConditions: Series options, not confirmation of every wetted material or coolant approval for one pair |
| Series pressure temperature reference | MQDB series summary lists working pressure 0–100 psi and working temperature -40 to +110 °C; the selected seal, pair and coolant require configuration review.Conditions: Manufacturer series summary; not a combined end-code and coolant approval |
Specifications apply to the named product and stated configuration; final supply details are agreed in the quote.