Part number XW-ES2-10H1
A coiled, connector-terminated leak-sensing line for use with a compatible locating controller. The documented XW-ES2-10H1 cable is 6.0 mm in diameter and has a listed resistance of 13 Ω/m.
- Cable diameter
- 6.0 mm
- Cable resistance
- 13 ohm/m
- Operating temperature
- -20 to 75 °C
- Construction
- Four conductors; two conductive fluoropolymer-covered sensing wires around a helical core
Xiangwei
XW-ES2-10H1
Leak Detection Components
Specifications
XW-ES2-10H1
| Parameter | Documented value / configuration |
|---|---|
| Model identity | XW-ES2-10H1 locating leak detection cable |
| System interface | Used with a compatible Xiangwei locating leak controller for position reporting |
| Detection coverage | Liquid contact can be detected along any position of the sensing cable when connected to a compatible Xiangwei locating leak controller; the maker's tap-water alarm criterion is at least 30 mm wetted cable lengthConditions: Manufacturer's tap-water reference condition only; detection of a different coolant, conductivity, cable route or controller combination requires its own test |