Leak Detection Components

Xiangwei Helical Locating Leak-Sensing Cable

Part number XW-ES2-10H1

A coiled, connector-terminated leak-sensing line for use with a compatible locating controller. The documented XW-ES2-10H1 cable is 6.0 mm in diameter and has a listed resistance of 13 Ω/m.

Cable diameter
6.0 mm
Cable resistance
13 ohm/m
Operating temperature
-20 to 75 °C
Construction
Four conductors; two conductive fluoropolymer-covered sensing wires around a helical core
XW-ES2-10H1

Xiangwei

XW-ES2-10H1

Leak Detection Components

Specifications

XW-ES2-10H1

ParameterDocumented value / configuration
Model identityXW-ES2-10H1 locating leak detection cable
System interfaceUsed with a compatible Xiangwei locating leak controller for position reporting
Detection coverageLiquid contact can be detected along any position of the sensing cable when connected to a compatible Xiangwei locating leak controller; the maker's tap-water alarm criterion is at least 30 mm wetted cable lengthConditions: Manufacturer's tap-water reference condition only; detection of a different coolant, conductivity, cable route or controller combination requires its own test

Specifications apply to the named product and stated configuration; final supply details are agreed in the quote.