Technical selection
Specifications and configuration
Reference — Xinda mixed-metal three-plate cooling circuit example
| Parameter | Documented value / configuration |
|---|---|
| Assembly composition | Two aluminum cold plates, one copper cold plate and connecting stainless tubingConditions: scope: Manufacturer-described pictured example, not a standard fixed bill of materials or tested site assembly |
| Listed plate materials | Copper C1100 and aluminum AL3003 listed for cold-plate componentsConditions: scope: Supplier page; plate-specific allocation and tube alloy require a controlled bill of materials |
| Supplier joining description | Vacuum brazing process listed as joining approachConditions: scope: Supplier claim only; joint design, filler, inspection and final qualification are not shown |
| Dimension control | Dimensions customized to the application drawingConditions: scope: No stock plate sizes or route coordinates are published for the pictured assembly |
Manufacturer reference configuration. Values and conditions apply to the named reference; the supplied configuration requires separate confirmation.
Overview
This actual pictured configuration joins three cold-plate positions into one server cooling assembly. It is a sourcing reference for a drawing-defined circuit, not a prequalified site design or stock item.
Construction and interfaces
The manufacturer describes two aluminum plates, one copper plate and connecting stainless tubing. Its material table lists C1100 copper and AL3003 aluminum; the exact allocation, joining filler and final wetted bill of materials need confirmation.
Selection
Compare all three heat-source contact footprints, rack-space constraints, tube route and the supply/return connection before selecting a comparable assembly. Mixed-metal coolant compatibility must be assessed for the actual fluid and surface treatment.
Configuration options
Plate footprints, tube route, end interfaces, mounting and cleaning are drawing-controlled inputs. The page calls dimensions customizable but does not publish a standard dimensional range or interchangeable plate kit.
Application limits
The supplier mentions vacuum brazing, but no joint drawing, pressure/leak acceptance value or condition-complete thermal result is supplied. Do not adopt absolute leakage or performance language from marketing copy.