Private previewCandidate · Draft · Noindex. Reference configuration; supply and public media use require confirmation.

LCP-000015 / Product configuration

Semi-Automatic Ball-Locking Quick Disconnect — CGQ Series

A two-part direct-insertion CGQ reference with a steel-ball locking mechanism and multiple documented model sizes, distinguished from steel-pin MQD and external-retention blind-mate couplings.

Listed temperature range
-55 to 120 degC
Size specific recommended flow
CGQ03 2.1; CGQ04 3.8; CGQ05 5.9; CGQ06 8.5; CGQ08 15.1; CGQ10 23.5; CGQ12 33.9; CGQ15 53; CGQ20 94.2; CGQ25 135 L/min
Documented connection variants
Threaded socket and plug options are shown separately by CGQ size and part code
Size specific socket plug end examples
CGQ03 stainless-code socket CGQ03.1342-G18 and plug CGQ03.7342-G18 are separately tabulated with G1/8 male-thread ends; other size, material and hose-end codes differ
Listed shell and seal options
CGQ order-code tables separate aluminum-alloy and stainless-steel columns; series summary lists EPDM and FVMQ sealing-ring options

Technical selection

Specifications and configuration

Reference — CGQ series

ParameterDocumented value / configuration
Engagement mechanismSteel-ball locking with direct insertionConditions: scope: semi-automatic manufacturer series description
Listed temperature range-55 to 120 degCConditions: scope: series summary; pressure, coolant and seal pairing require exact variant review
Size specific recommended flowCGQ03 2.1; CGQ04 3.8; CGQ05 5.9; CGQ06 8.5; CGQ08 15.1; CGQ10 23.5; CGQ12 33.9; CGQ15 53; CGQ20 94.2; CGQ25 135 L/minConditions: scope: separate model rows, water 20 degC, plug-to-socket, 5 m/s velocity criterion; not one rating
Documented connection variantsThreaded socket and plug options are shown separately by CGQ size and part codeConditions: scope: mating half and end geometry must match one controlled order code
Size specific socket plug end examplesCGQ03 stainless-code socket CGQ03.1342-G18 and plug CGQ03.7342-G18 are separately tabulated with G1/8 male-thread ends; other size, material and hose-end codes differConditions: scope: Example pair rows only, not proof every CGQ half or depicted image uses G1/8
Listed shell and seal optionsCGQ order-code tables separate aluminum-alloy and stainless-steel columns; series summary lists EPDM and FVMQ sealing-ring optionsConditions: scope: Material and seal depend on selected half codes; wetted compatibility not universal

Manufacturer series reference. Confirm the exact order code, mating parts and stated conditions for the quoted configuration.

Overview

A CGQ-style connector combines direct insertion with automatic steel-ball engagement. The manufacturer image shows separate mating halves, making the buyer's pair selection and end-form requirements explicit.

Construction and interfaces

The series illustration has distinct socket and plug bodies and coloured identification rings. Their material and end termination are order-code choices; the reference visual cannot identify which exact model row it depicts.

Selection

The catalogue lists many CGQ size-specific recommended water flows, from compact to larger variants, under one defined test criterion. Use the relevant row and pressure-drop curve, not the endpoints as a blanket deliverable range.

Configuration options

Specify the exact CGQ size, both mating half codes, threaded or tube-side connection and colour identification as applicable. The source's separate part-code tables must govern the selected assembly.

Application limits

A broad manufacturer temperature statement does not establish coolant compatibility or the operating pressure at that extreme. Appearance, catalogue part code and final fluid-contact materials must be reconciled before quoting.