Private previewCandidate · Draft · Noindex. Reference configuration; supply and public media use require confirmation.

Liquid cooling component family

Liquid Cooling Hose Assemblies

A candidate family page for configured hose, end connections, routing, and assembly validation.

Material
Zinc-free peroxide-cured EPDM is used in Data Master and MegaFlex family descriptions.
Inside diameter
Data Master: 7/32 to 1 in; Eco: 3/16, 1/4, 3/8 in; MegaFlex: up to 4 in
Working pressure
627-6-RL: 150 psi; 801-16: 200 psi; 801-4: 350 psi
Temperature
-40°C to 100°C for Series 627
Working pressure
10 bar

Technical selection

Specifications and configuration

Reference — Parker Hannifin — 627

ParameterDocumented value / configuration
ConstructionPeroxide-cured EPDM tube with textile reinforcement is one documented liquid-cooling construction.
Temperature-40°C to 100°C for Series 627

Reference — Gates — Data Master family

ParameterDocumented value / configuration
MaterialZinc-free peroxide-cured EPDM is used in Data Master and MegaFlex family descriptions.
Inside diameterData Master: 7/32 to 1 in; Eco: 3/16, 1/4, 3/8 in; MegaFlex: up to 4 in

Reference — Parker Hannifin — 801 and 627 examples

ParameterDocumented value / configuration
Working pressure627-6-RL: 150 psi; 801-16: 200 psi; 801-4: 350 psiConditions: warning: values vary by part number and construction

Reference — Parker Hannifin — bulletin scope

ParameterDocumented value / configuration
Coolantdeionized water with inhibitors/biocides; water/propylene glycol PG25

Reference — Hydraflex — HQDC-4-6

ParameterDocumented value / configuration
Hose boremetric: 6; nominal inch label: 1/4 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure10 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure30 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — HQDC-4-10

ParameterDocumented value / configuration
Hose boremetric: 10; nominal inch label: 3/8 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure10 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure30 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — HQDC-4-13

ParameterDocumented value / configuration
Hose boremetric: 13; nominal inch label: 1/2 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure10 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure30 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — HQDC-4-20

ParameterDocumented value / configuration
Hose boremetric: 19; nominal inch label: 3/4 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure10 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure30 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — HQDC-4-25

ParameterDocumented value / configuration
Hose boremetric: 25; nominal inch label: 1 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure10 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure30 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — HQDC-4-32

ParameterDocumented value / configuration
Hose boremetric: 32; nominal inch label: 1 1/4 mmConditions: DataCool hose part number; nominal label: Inch designation is nominal, not an exact conversion
Working pressure6 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope
Burst pressure20 barConditions: DataCool hose part number; application: DataCool rear-door cooling hose, not MFC assemblies; limit: Burst figure is not allowable operating pressure; test conditions: Fluid, temperature and end-connection rating are not specified by this table; no inferred pressure-temperature envelope

Reference — Hydraflex — DataCool fitting options

ParameterDocumented value / configuration
Minimum fitting boreDN06: 4.2; DN10: 6.7; DN13: 8.7; DN19: 14.8; DN25: 19.8; DN32: 25.5 mmConditions: DN labels and minimum flow passage, not outside diameter; scope: Independent fitting-size reference, not a complete assembly ordering code

Reference — MFC — Liquid Cooling Assemblies (March 2026)

ParameterDocumented value / configuration
Metal hose constructionCorrugated stainless-steel flexible hose assemblies with configured end fittingsConditions: Metal hose; scope: Metal hose variant, not silicone hose
Rubber hose materialPeroxide-cured EPDMConditions: Rubber hose; scope: Brochure test-equipment capacity is not an assembly pressure rating

Candidate Product-family draft. Configuration, availability and acceptance are established for the requested item.

Component scope

A liquid-cooling hose assembly combines a selected hose construction with controlled ends and finished geometry. Hose-body ratings do not automatically describe a crimped or otherwise terminated assembly.

Configuration and selection

Specify hose ID and envelope, finished length, end types and orientation, route and bend limits, coolant, pressure and temperature. Define cleanliness, inspection, assembly test and packaging for the quoted configuration.

Define before quotation

  • Hose construction and wetted materials
  • End connections and orientation
  • Routing, bend, abrasion, and service constraints
  • Pressure, leakage, cleanliness, packaging, and quantity

Evidence and supply boundary

Exact model, interfaces, materials, coolant compatibility, operating conditions, tests, documentation, quantity and supply scope require configuration-specific review. No stock, certification or performance is implied by this draft.