Private previewCandidate · Draft · Noindex. Reference configuration; supply and public media use require confirmation.

LCP-000005 / Product configuration

Multi-Circuit Liquid Leak Detection Controller

A separately housed leak-detection panel that monitors sensing-cable circuits and provides alarm outputs; the pictured device is an exact model reference, not a complete site shutdown system.

Output
eight programmable alarm relays; power-fail relay; Modbus over RS232/RS422/RS485
Coverage
location accuracy m: 1; maximum per circuit m: 600; maximum total m: 1800
Alarm boundary
Panel reports leak or cable-break state; site shutdown/interlock logic remains a separate system design decision.
Test method
Built-in test function scans the system and connected cable lengths; commissioning acceptance needs a documented procedure.

Technical selection

Specifications and configuration

Reference — FG-SYS

ParameterDocumented value / configuration
Coveragelocation accuracy m: 1; maximum per circuit m: 600; maximum total m: 1800
Outputeight programmable alarm relays; power-fail relay; Modbus over RS232/RS422/RS485
Alarm boundaryPanel reports leak or cable-break state; site shutdown/interlock logic remains a separate system design decision.
Test methodBuilt-in test function scans the system and connected cable lengths; commissioning acceptance needs a documented procedure.

Manufacturer reference configuration. Values and conditions apply to the named reference; the supplied configuration requires separate confirmation.

Overview

This controller supervises connected leak-sensing cable circuits and reports leakage or cable-fault conditions to an external control system. It is a monitoring component, not proof of end-to-end leak prevention.

Construction and interfaces

The pictured exact reference is a wall-mounted control enclosure with a local display and connection points for sensing and output wiring. Cable type, circuit layout and electrical supply must match the controlled installation documents.

Selection

Design the cable coverage and circuit lengths around the actual equipment area, including service and maintenance access. Alarm relays and serial interfaces must be matched to the buyer's building or rack control architecture.

Configuration options

The documented controller supports multiple alarm outputs and serial communication paths. This does not mean every sensing cable, wiring topology or site interlock is included in the controller order.

Application limits

The controller reports an alarm state; shutdown logic, alarm routing, commissioning tests and response ownership are separate system decisions. Electrical power details require rechecking because the stored source text contains an encoding defect.